Hager ADA166U RCBO Electronic 1P 10kA C Curve-16A, 30mA Type A(AC & Pulsating DC Sensitive)1M
New
30

https://hager.com/intl-en/products/information/ada166u-rcbo-1p-10ka-c-16a-30ma-type-a-1m

Technical properties

Archi­tec­ture
  • Neutral posi­tion
    right
  • Number of protected poles
    1
  • Number of poles
    1 P
  • Type of pole
    1 P
  • Curve
    C
Func­tions
  • Concur­rently switching N-neutral
    No
Config­ur­a­tion
  • Number of modules
    1
Main elec­trical features
  • Rated short circuit breaking capa­city Icn AC according IEC60898-1
    10 kA
  • Rated oper­a­tional voltage Ue
    230 / 240 V
  • Frequency
    50 Hz
Voltage
  • Rated insu­la­tion voltage
    250 V
  • Max oper­ating voltage
    253 V
  • Rated impulse with­stand voltage
    4000 V
Elec­tric current
  • Rated residual oper­ating current
    30 mA
  • Rated current
    16 A
  • Breaking and opening capa­city
    6 kA
  • min/maxi threshold value of the AC thermal oper­a­tion
    1.13 / 1.45 In
  • Magnetic regu­lating currrent
    5 / 10 In
  • Rated short circuit breaking capa­city Icn under 230V AC according IEC60898-1
    10 kA
Elec­tric current / temper­ature
  • Rating current -25°C
    22.23 A
  • Rating current -20°C
    21.74 A
  • Rating current -15°C
    21.23 A
  • Rating current -10°C
    20.72 A
  • Rating current -5°C
    20.19 A
  • Rating current 0°C
    19.64 A
  • Rating current 5°C
    19.08 A
  • Rating current 10°C
    18.51 A
  • Rating current 15°C
    17.91 A
  • Rating current 20°C
    17.3 A
  • Rating current 25°C
    16.66 A
  • Rating current 30°C
    16 A
  • Rating current 35°C
    15.38 A
  • Rating current 40°C
    14.75 A
  • Rating current 45°C
    14.13 A
  • Rating current 50°C
    13.5 A
  • Rating current 55°C
    12.88 A
  • Rating current 60°C
    12.25 A
Current correc­tion factors
  • Correc­tion factor of rating current for 2 devices placed side-by-side
    1
  • Correc­tion factor of rating current for 3 devices placed side-by-side
    0.95
  • Correc­tion factor of rating current for 4 and 5 devices placed side-by-side
    0.9
  • Correc­tion factor of rating current for 6 devices placed side-by-side
    0.85
Dimen­sions
  • Depth of installed product
    70 mm
  • Height of installed product
    115 mm
  • Width of installed product
    17.8 mm
Frequency
  • Frequency
    50 Hz
Power
  • Total power loss under IN
    4.74 W
  • Power loss per pole at In
    2.88 W
Trip­ping
  • Protected against nuis­ance trip­ping
    No
Endur­ance
  • Elec­tric endur­ance in number of cycles
    2000
  • Number of mech­an­ical oper­a­tions
    1000
Install­a­tion, mounting
  • Tight­ening torque
    2,1Nm
  • Type of top rail clip for modular devices
    NA
  • Type of bottom rail clip for modular devices
    metallic isol­ated
  • Top remov­ab­ility for modular devices
    No
Connec­tion
  • Connec­tion cross-sec­tion at output with screw, for flex­ible conductor
    1 / 16 mm²
  • Connec­tion cross-sec­tion at output with screw, for massive conductor
    1 / 25 mm²
  • Connec­tion cross-sec­tion for rigid conductor, upstream terminals with screws
    1 / 25 mm²
  • Connec­tion cross-sec­tion of the access with screws, with flex­ible conductor
    1 / 16 mm²
Equip­ment
  • With trans­parent product label holder
    No
Stand­ards
  • Standard text
    EN 61009-1 ; IEC 61009-1
Safety
  • Residual current type
    A
  • REACH conform
    No
  • RoHS conform
    Yes
  • Halogen free
    No
Use condi­tions
  • Degree of pollu­tion according to IEC 60664 / IEC 60947-2
    2
  • Class of energy limit­a­tion I²t
    3
  • Alti­tude
    2000 m
  • Air humidity protec­tion
    Execu­tion II

Overview